# Installing Smart Breakers

Available in 15, 20, 30, 40, 50, and 60A, these 2-pole smart breakers feature load control, revenue-grade metering (±0.5%) and GFCI protection. A maximum of **8** breakers can be used per Lunar System, and can be installed inside the Lunar Bridge or any BR-style Eaten panels.

<img src="https://mintcdn.com/lunarenergy/ur4SEtH7YEWeM2cq/images/eaton-config-diagram.png?fit=max&auto=format&n=ur4SEtH7YEWeM2cq&q=85&s=f8106c8eae4116b1b08ad5dba9a80283" alt="Smart Breaker Configuration" width="1786" height="771" data-path="images/eaton-config-diagram.png" />

## Communication Range

Smart breakers communicate wirelessly with the Lunar Bridge or Lunar Meter Socket Adapter Controller (MSA Controller). They can be installed inside the Lunar Bridge or in any [compatible EATON subpanel](https://www.eaton.com/us/en-us/products/electrical-circuit-protection/circuit-breakers/ableedge-smart-breaker-compatibility.html) with maximum distances as detailed below:

| Configuration                     | **Maximum Distance to Lunar Bridge/MSA Controller** |
| :-------------------------------- | :-------------------------------------------------- |
| Free air                          | 75 ft (23 m)                                        |
| Through 1 wall (wood / drywall)   | 30 ft (9 m)                                         |
| Through 1 wall (concrete / brick) | 10 ft (3 m)                                         |

## AC-Coupled PV Requirements

| Requirements                    | Description                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            |
| :------------------------------ | :----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Maximum AC PV in Backup**     | 11.5 kW combined of non-Lunar AC PV<br /><br />**Examples**<br />(1) 1 x 7.6kW PV inverter and 1 x 3.8kW PV inverter<br />(2) 3 x 3.8kW PV inverters<br /><Note>Up to **8** smart breakers can be used to support multiple AC PV connections. For improved inverter-level monitoring and to prevent ground/arc faults from shutting down all PV, a dedicated smart breaker per AC PV system is recommended. A PV combiner subpanel with a single smart breaker is allowed, but not recommended.</Note> |
| **Maximum AC PV in Non-Backup** | No limit <br /><Note>All non-backup loads and non-backup AC PV must be on the load side of the Lunar Rogowski Coils, along with the backup loads and backup AC PV. Refer to the [Rogowski Coil (CTs) for the Lunar System](https://documents.lunarenergy.com/rogowski-coils-cts-for-the-lunar-system) Application Note.</Note>                                                                                                                                                                         |
| **Compatible PV Inverters**     | All CEC-listed models and makes.                                                                                                                                                                                                                                                                                                                                                                                                                                                                       |
| **Lunar DC PV Size**            | 0 - 15kWdc. <br /><Note>DC PV is not required for the Lunar System. DC PV size is independent of AC PV size. Maximizer stringing rules apply.</Note>                                                                                                                                                                                                                                                                                                                                                   |

### AC PV Metering

Smart breaker acts as a metering device for AC PV. No additional CT for PV circuits.
<Note>Rogowski coils may still be required to monitor site import and export for partial home backup (i.e. AC PV in non-backup).</Note>

### Line Side Tap

Install breaker between fused disconnect and AC PV, by following these steps:

1. Turning the fused disconnect OFF.
2. Splicing the inverter output wires inside the inverter enclosure.
3. Splicing there and back to an adjacent 2-space subpanel with a smart breaker.

<Note>Utility coordinated disconnect is not required. It does not touch or modify the tap, nor touch the wires between the tap and the fused disconnect.</Note>

## Wiring Smart Breakers

<img src="https://mintcdn.com/lunarenergy/ur4SEtH7YEWeM2cq/images/eaton-wiring-diagram.png?fit=max&auto=format&n=ur4SEtH7YEWeM2cq&q=85&s=cb1e3d5c9f6d7bdfcfada39a18dd4927" alt="Smart Breaker Wiring Diagram" width="1999" height="1320" data-path="images/eaton-wiring-diagram.png" />

<Danger>
  To avoid nuisance GFCI tripping, connect the load neutral wire directly to the breaker and the breaker's neutral pigtail to the neutral bar.
</Danger>